1.1 Background to the project. 2
1.2 Aims of this research. 3
1.3 Outline of thesis chapters. 4
2.1 Introduction. 8
2.2 Traditional Design. 8
2.2.1 The fire resistance test. 82.3 The Swedish Design Guide. 24
2.2.2 Critical steel temperature. 11
2.2.3 Fire protection. 11
2.2.4 Shortcomings of the fire resistance test. 13
2.2.5 Equivalent fire exposure. 14
2.2.6 Natural Fire method. 20
2.2.7 Fire resistance by calculation. 20
2.4 Performance based design. 25
2.5 Factors affecting the behaviour of structures in fire. 28
2.5.1 Mechanical properties of steel at elevated temperatures. 282.6 Research into the behaviour of single elements of structure in fire. 41
2.5.2 Mechanical properties of concrete at elevated temperature. 32
2.5.3 Thermal Bowing and Thermal Expansion. 36
2.5.4 Redundancy. 40
2.5.5 Loading. 40
2.6.1 Computer models for structures. 412.7 Frame Analysis. 51
2.6.2 Columns. 42
2.6.3 Beams. 47
2.6.4 Slabs. 48
2.8 Conclusion. 54
3.1 Introduction. 56
3.2 Natural Fire Curves. 56
3.3 Compartment Fires. 57
3.3.1 The Pre-flashover Fire. 593.4 The burning regime: Ventilation vs. Fuel controlled fires. 63
3.3.2 The Post-flashover fire. 62
3.3.3 The decay period. 62
3.4.1 Opening factor. 643.5 CIB compartment fire experiments. 66
3.4.2 Differentiating between fuel and ventilation controlled fires. 64
3.4.3 Fuel controlled fire. 65
3.6 Compartment fire modelling. 67
3.6.1 Model types. 673.7 Parametric T-t curves. 77
3.6.2 Zone modelling. 68
3.6.3 Heat balance equation for an enclosure (Pettersson et al, 1976 [195]). 70
3.6.4 Empirical/Characteristic temperature curves. 74
3.7.1 The Parametric T-t curve in EC1. [74] 773.8 The Natural Fire Safety Concept. [224] 81
3.7.2 Comparison with compartment fire test data. 80
3.9 Other factors influencing the rate of heat release in a compartment fire. 84
3.9.1 Vent location. 843.10 Compartment fire models for computers. 88
3.9.2 Fuel load. 85
3.9.3 Compartment dimensions. 86
3.9.4 Thermal inertia of the compartment boundaries, kpc. 87
3.10.1 Zone models for computers. 883.11 Heat Transfer. 91
3.10.2 CED models. [85] [119] [196] [233] 90
3.11.1 The Heat Transfer Equations. 913.12 Thermal properties of materials. 94
3.11.2 Solving the Heat Transfer Equations. 93
3.12.1 Steel. 953.13 Predicting steel temperatures. 98
3.12.2 Concrete. 96
3.13.1 Hp/A Concept. 993.14 Modelling heat transfer in concrete. 102
3.13.2 Simple heat transfer models. 100
3.13.3 Uninsulated steel. [161] 100
3.13.4 Insulated steel. 101
3.13.5 Nomograms. 102
3.15 Conclusions. 105
4.1 Introduction. 108
4.2 Case studies. 108
4.2.1 Broadgate Phase 8. 1084.3 Fire tests. 109
4.2.2 Churchill Plaza building, Basingstoke. 109
4.3.1 BHP William Street fire tests, Melbourne. [197] 1094.4 The PIT Project. 118
4.3.2 Stuttgart-Vaihingen University fire tests, Germany. 110
4.3.3 Cardington frame fire tests. 111
4.4.1 The numerical models. 1214.5 Numerical Modelling at Sheffield University. 133
4.4.2 Theoretical analyses. 131
4.4.3 Parametric studies. 131
4.4.4 Analysis of the raw test data by British Steel. 132
4.4.5 Conclusions of the PIT project. 132
4.6 Developments in Europe. 134
4.6.1 ECSC Project. [246] 1344.7 Design guidance. 135
4.7.1 SCI design guide. 1354.8 Conclusion. 138
4.7.2 Design guidance developed in New Zealand. 136
5.1 Introduction. 141
5.2 Solving Transient Conduction using the Finite Element Method. 141
5.2.1 The Governing Differential Equations and Finite Element Formulation. 1425.3 Modelling Phase Change. 143
5.4 Interface Elements for modelling heat transfer between two materials. 144
5.5 The Models. 144
5.5.1 Material Properties. 1455.6 Modelling and Analysis. 146
5.6.1 Model 1: No Metal Deck. 1465.7 Model 2: Including the Metal Deck. 156
5.6.2 Hottest and Coolest slab. 147
5.6.3 Sensitivity Analyses. 149
5.6.4 Summary. 154
5.6.5 Correlation with measured temperatures. 156
5.7.1 Prediction of Test 4 Temperatures. 1605.8 Modelling Edge beams. 160
5.8.1 Edge beams in British Steel Test 3. 1635.9 Conclusions. 169
5.8.2 Edge beams in British Steel Test 4. 165
6.1 Introduction. 174
6.2 Thermal expansion and thermal bowing Interaction. 174
6.2.1 The heating regime. 1756.3 Runaway in axially unrestrained and axially restrained beams. 193
6.2.2 Thermal expansion. 175
6.2.3 Thermal Bowing. 179
6.2.4 Combined thermal expansion and thermal bowing. 181
6.2.5 Numerical analysis of thermal expansion and thermal bowing in a restrained beam. 183
6.2.6 Summary. 191
6.3.1 The impact of loading on "runaway" in a pinned beam. 1956.4 Conclusions. 202
6.3.2 Implications. 199
7.1 Introduction. 205
7.2 Effect of varying the slab thermal gradients in British Steel test 1. 205
7.2.1 Description of the fire compartment. 2057.3 Effect of varying the slab mean temperature in British Steel test 1. 219
7.2.2 The finite element model. 206
7.2.3 Slab gradient variation in longitudinal direction. 210
7.2.4 Slab gradient variation in transverse direction. 214
7.3.1 Slab mean temperature variation in longitudinal direction. 2197.4 Conclusions. 231
7.3.2 Mean temperature variation in transverse direction. 226
8.1 Introduction. 233
8.2 Analysis. 234
8.2.1 The generic frame. 2348.3 Parametric Studies. 244
8.2.2 Design fires. 234
8.2.3 Heat transfer. 235
8.2.4 Temperature loading. 236
8.2.5 The structural model. 238
8.2.6 The numerical model. 243
8.4 Results. 244
8.4.1 Short versus long post-flashover fires in the 2x2 bay frame with edge beams protected. 2448.5 Conclusions. 317
8.4.2 Impact of imposed loading on primary beam instability. 280
8.4.3 Impact of secondary beams on primary beam instability. 281
8.4.4 Simple beam study. 282
8.4.5 Effect of applied fire protection in a "long" post-flashover fire. 286
8.4.6 Effect of applied fire protection in a "short" post-flashover fire. 301
8.4.7 Behaviour of the slab. 312
9.1 Introduction. 321
9.2 The generic frame. 321
9.3 Compartment fires. 322
9.4 Temperature loading. 323
9.5 Scenarios tested. 323
9.6 Results. 324
9.6.1 Short versus long post-flashover fires in the 9x9 bay frame with the Edge beams unprotected. 3249.7 Large versus small frames. 356
9.6.2 Corner and Edge compartment fires in the 9 x 9 frame. 339
9.6.3 Effect of protection level under a "long" post-flashover fire in a large frame. 350
9.6.4 Response of the beams. 352
9.6.5 Slab behaviour. 352
9.6.6 Summary. 356
9.8 Conclusions. 358
10.1 Introduction. 361
10.2 Summary and Conclusions. 361
10.3 Further work. 366
10.3.1 Further development of FEAST. 366
10.3.2 Further parametric studies. 366
10.3.3 Spreading fires. 367
10.3.4 Cardington Frame Fire Test Data. 367
10.3.5 Future fire tests. 369
10.3.6 Development of design codes 369
| Combustible content (wood equivalent) | Equivalent | Standard fire duration | |
|---|---|---|---|
| (lb/ft2) | (kg/m2) | (kJ/m2 x 10-6) | (h) |
| 10 | 49 | 0.90 | 1 |
| 15 | 73 | 1.34 | 1.5 |
| 20 | 98 | 1.80 | 2 |
| 30 | 146 | 2.69 | 3 |
| 40 | 195 | 3.59 | 4.5 |
| 50 | 244 | 4.49 | 6 |
| 60 | 293 | 5.39 | 7.5 |
| Dry thickness in mm to provide fire resistance of: | ||||
|---|---|---|---|---|
| Hp/A up to | 1/2 hour | 1 hour | 3/2 hour | 2 hour |
| 30 | 10 | 10 | 10 | 11 |
| 110 | 10 | 10 | 18 | 25 |
| 250 | 10 | 13 | 24 | 34 |